I know it is an unusual design. It is for a very old subway station. There is no way to build ventilation shaft at this time. The only way I can think about is to run a very long duct.
No, it is not a homework. It is a subway station renovation project. The washroom is located in 20 metres below ground. The exhaust air duct starts from the washroom, through a few rooms at the same floor, then rises up 10 meters to the concourse level, the horizontal run of the duct in...
Hi, here is the fan curve and data sheet.
Thanks.http://files.engineering.com/getfile.aspx?folder=8099686f-e35b-4d49-a319-36115295dd69&file=GREENHECK_BSQ-80-5.pdf
Hi, I am sizing an exhaust fan for a washroom located 20 meters below ground in a subway station. The horizontal run of the exhaust ducg is 80 meters, plus 8 elbows. The duct ends up at the exterior wall above ground. The exhaust air is 300CFM.
My calculation shows me the pressure drop of the...