I'm building a moly glass furnace that requires a 40kva transformer. The transformer might need to be inside my building.
How do I determine emf...radiation levels from the transformer and the safety protocols...distance from, shielding, etc.
Thanks,Virgil
a little more on what I currently (the 100lber)have:
controller has 4-20 milliamp output capability
current limiting scr
transformer plate reads:
marcus transformers
model 15G45-20T
240 primary
45 secondary
kva 15
hz 60
single phase
type wm
temp 150 C
class 220
spec. 9155
connect: cu/al...
thanks for the replies
7anoter4
the underground line from the splitter box is about 400ft...and 700feet before that and it looks like a bigger box at that location...MAYBE a transformer???...I don't know about the utility company transformers. They said I had more than enough for 400amps...did...
As on a previous thread I'm building a new 400lb studio glass furnace to replace the current 100lb glass furnace.
Now going Moly elements
9 elements 9/18 312/500 60amp 12.5 volts each
wired in 3 series of 3each
40 kva transformer 4 to 1 step down
furnace will run on separate 200amp...
So, after a couple of weeks of educating myself on the SIC element system and molybdenum disilicide (MoSi2) element system I will be going with the Moly elements. Initial costs are much more, but should be cheaper in the long run...longer element life to go with 10 year or more of life of the...
Propane in this application (studio glass furnace) is at least twice as expensive.
Three-phase in not available.
With further discussions today with Larry at Watlow it looks like I'll be using the SCR with current limiting and be able to lower the amps. This will reduce costs and take care of...
I’m in the process of building a studio glass furnace and have concerns about the set-up for the control system.
I have 240V single phase
400amps into the building off a 350 aluminum underground line.
Furnace will be on a on a separate 200 amp circuit. Breaker in the box and then fused...