  1. viperneo

    Circuit Protection....

    Cool, thx. After DRWeig post, I suspect that to be the problem. I'll see if this is the case fri and hopefully it'll be solved. Thanks guys and gals.
  2. viperneo

    Circuit Protection....

    Keith, Freq is not the problem b/c the pump had operated under the gen power, so I don't think voltage and size is a problem either. It may just be what dave said, a delay issue. I would like to hear more ideas on what the problem may be. Situation: ATS feed 15hp pump. Between ats and...
  3. viperneo

    Circuit Protection....

    I have a problem with my cb tripping at a transfer. I have a 3 ph Fuse (30A Ferraz Class CC) that blows up when there's a upstream transfer from an ATS. The fuse is protecting a pump, and at normal condition (util power) the pump is able to operate as usual. But when power is out or a...