I understand Article 551. I'm just a little confused about the tap rule. Once my 3/0 cable leave the 200A bkr and lands in the first 125A pedestal lugs, then the 3/0 leaves the pedestal (via lugs) for the next pedestal and so on. (see attached) Once the 3/0 leaves the first 125A Pedestal does...
I have been tasked to design the electrical system for a small RV park. I'm planning on using RV pedestals that are 240/120VAC, 125A with 50A 2-pole, 30A 1-pole, 20A 1-pole breakers and receptacles on the pedestal. My question is can I feed (loop feed) six of these pedestals from one 200A...