  1. koubi

    Control ratio

    Thanks JLSeagull but wwhat about below 10% of the valves travel? It is about dual valve high load - low load arrangement application. Lets say that we have two control valves with linear characteristic, one with metal to metal sealing and one with soft sealing. It is assumed that soft sealing...
  2. koubi

    Variable primary chilled water loop

    Sorry I missed the point that all the chillers have different sizes. With this fact and a fact that the pumps are headed you have very demanding installation. Flows through the chillers should be dynamically balanced with automatic balancing valves equipped with modulating actuator. Valves...
  3. koubi

    HEX characteristic

    Are there any equations for calculation of air to water cooling coil characteristic?
  4. koubi

    Variable primary chilled water loop

    From hydronic point of view,you should consider following points: How are the pumps configured; are they dedicated (1 chiller 1 pump) or headered? Are all chillers equaly sized? How is bypass line and bypass control valve designed? Is flow meter in use and where it is located?
  5. koubi

    Control ratio

    What is typical control ratio of a control valve for HVAC application with metal to metal sealing? I understand that a control valve with metal to metal sealing should have higher range ability compared to the one with soft sealing.