  1. CoolB00Yz

    Ground Fault 50N Nuisance Trip Dring Starting

    SOLVED!! Thank you for your input. We did tried couple of times to increase the TD and trip setting. Below shows our trial and error. 10A 50ms - trip 20A 50ms - trip 20A 100ms - trip 30A 100ms - trip 40A 100ms - OK both motors running. We found the CBCT IN goes to max of 34A which explains the...
  2. CoolB00Yz

    Ground Fault 50N Nuisance Trip Dring Starting

    Thank you wcaseyharman. will try to change the CBCT and see if we can run the motors. A typical electrical engineer
  3. CoolB00Yz

    Ground Fault 50N Nuisance Trip Dring Starting

    Hi dpc, current varies from 10A to 30A in CBCT. If sum all phases, it doesn't add up to be the same. We suspect the CBCT and will try to change today. Trip is while starting - 10ms, 20ms and 30ms during starting depends on the time delay set. Yes, CT programmed correctly 50:5. SEL terminalogy -...
  4. CoolB00Yz

    Ground Fault 50N Nuisance Trip Dring Starting

    Hi davidbeach - NO as shields were removed prior going into CBCT. Only the conductors passed through CBCT.
  5. CoolB00Yz

    Ground Fault 50N Nuisance Trip Dring Starting

    Hey Guys. We are commissioning 2 4000HP motors via 4KV controlgear. The issue we are facing is that both motors keep tripping during commissioning performing motor solo run. They are both tripping on 50N Ground Fault via SEL-710 relay. Ground fault current detected via CBCT 50:5. The setting...