I have a 3.5 MW motor, syncronous, with two sleeve bearings, (zoelern manufacturer) and i have temperatures up to 93 º C, and the manufacturer of the motor, says me that i could put the alarm temperature on 95ºC and the stop on 100 º C, this seems to be too high, does somebody knows about some...
where could i get a sizing program on internet? yes, my mechanical calculations,talks me on 2193 kva, and 1500 kw nominal, but if i get all except one, in example 450 kw i get with the starting current a 3,8 MVA... how could i size the gen set? i don´t know....
hi,
I want to start up 3- 300 kw (272 start up current cos 0,7) motor, 1- 90 kw ( 68 A start up current, cos 0,72), 1- 450 kw ( 396 A start up current cos 0,7) and the voltage is 4160 Volts... we are thinking on starting up with direct start and a generator driven by a diesel motor.
thanks...
...my question is What do you think about idea? i think the current will be really low, and is it possible to calculate the time for accelerating..... if we have a load if we have a load that starts with 0 and changes with the formula
181+ (0,0002*n^2) where n is speed rpm
thanks for your...
I have a problem with a VFD and a syncronous motor permanet magnets (10 kw 100 hz 400 V), i had asked before some tips, now i could start up without flashing... with a 10khz,the motor have electrical arc between rotor and stator.... and then, i reduce to 3 khz the electrical arc dissaperar, but...
ok. i forget to mention, i got 2 units else, and they are more or less shared, little diferences... 5 amps or so, but i don´t know if the manufacturer of the wire is the same... the section, yes.
and about this.... about geometric configuration, what could be the expected difference in the worst situation? i don´t know if this could be mesasured or calculated?
maybe if the installer used a cheap wire? this theorical resistivity would change? do you think this is cause of resistivity of cooper?
and yes... i see the wires going out of the generators connection box and then go through the floor till the bus bars.... and seems to be the same, except that...
and what does the electrical code says about this? cause i want to ask the guy that do the installation...cause now the supervisor didn´t accept us the instalation.....
But my question is why this difference? cause the lenght is more or less the same, maybe mutual inductance? could somebody explain this mechanical guy this?
yeah, i have no pic, but the distance is the same, they go to the same bus bar and in the other connection point, they goes to the same bar... what is the difference on distances that make a difference of 60 A.? the distance between generator and bus bars are 100 m.