Am working on a pretreatment train and am experiencing significant increase in TOC across the multimedia filter beds. Water is chlorinated for breakpoint chlorination and enters the filter bed (sand and anthracite) with about 9 ppm free chlorine.
We see TOC jumping from around 1.3 to 9 through...
Quark,
The influent to the still is the effluent from the softeners plus some bisulfite to dechlorinate. Conductivity is probably on order of 200 mmhos
working with a customer who is experiencing high conductivity in WFI stills following his pretreatment train thinking it is possibly due to ammonia from not reaching breakpoint with chlorination. Train is city water influent, chlorination using industrial bleach to 5 ppm free chlorine, contact...