A bucholz relay operation,when DGA shows normal results may be due to the following causes.
1)Release of air trapped inside the transformer.
2)Sudden drop in atmospheric tmperature or sudden drop in
tmperture with a choked breather.
3) Vibration of b'relay.
After operation,if thereis gas found...