Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Recent content by tsccgy19

  1. tsccgy19

    Duct Static Pressure Mesurement

    Thanks for the info. The installers had the holes in the tube parallel to flow so I switched it around and have a stable reading. We are using a Building Automation System to control the VFD and the control seems great so far. In my experimentation, I drilled a hole in the duct beside the pitot...
  2. tsccgy19

    Duct Static Pressure Mesurement

    Hello Group, I am interested in measuring Duct Static pressure usint a Setra 0-5" WC 4-20mA pressure transmitter to control a VFD. How should I terminate my high pressure hose into the duct. I found at one of our suppliers what they call a Pitot tube which is about 4 inches long by and has...

Part and Inventory Search