If I have a 3 phase transformer rated at 30kVA, 600V primary, 120/208V secondary:
Ip=[30x1000]/[600x1.73]=28.9A (then multiply by 1.25 for code) and the cable size would be #8AWG
Is=[30x1000]/[208x1.73]=83.3A (then multiply by 1.25 for code) and the cable size would be #2AWG
And for a 1...