Recent content by scrudman

  1. scrudman

    bridge rectifier filter

    Thanks to all those posting. The motor was switched with 30 amp rated power relays, that the the windlass manufacturer insists theyve been using without problems-I am very doubtful. The failures were complete meltdown of contacts, and I immediately suspected improper switchgear for the app...
  2. scrudman

    bridge rectifier filter

    Thanks Scotty, The motor runs but the switching relays are failing every other month. I believe that this is due to inadequate relays for this app and I have already spec'd and ordered replacements, but I wanted to make sure that the lack of a cap wasn't a contributing factor, and that the...
  3. scrudman

    bridge rectifier filter

    I am working on a boat with a 120 vdc anchor windlass. I believe the motor to be 3 HP and the 120 vdc source is from a full wave bridge (120vac input). The output of the bridge has no capacitor. Should I install a capacitor and how do I determine the proper size?