Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Recent content by rwsmith99

  1. rwsmith99

    Evaporative cooling in greenhouse

    Quark and Louball, thanks for the posts. The issue has been resolved by changing all 4 fan motors in "A" to 3/4 hp motors, allowing a change in drive pullies from 3" to 3 1/2" (per fan mfr. recommendations.) The resulting increase in fan RPM boosted each fan's performance...
  2. rwsmith99

    Evaporative cooling in greenhouse

    I work at a research facility which uses several greenhouse facilities. There are two greenhouses side by side with nearly identical volumes. One ("A") is a gabled design and the other ("B") a semi-quonset (curved roof) design. Both are 30ft. in width and 100ft. in length...