Thanks everybody for your opinion. I have the latest of NFPA 14 and for me it is pretty clear what to do for hydraulics calculation when using 21/2" hoses, but when using 11/2" hoses it only says that you have to supply the topmost fire hose with 100 gpm at 65 psi and it does not stablish a...
Hello,
I am designing a small 5 story building and our fire autority has approve to uso one 11/2" fire hose at each floor. I have calculated pipes using a water demand of 100 gpm at 100 psi at the topmost fire hose. It this correct or do I have to add other demands from the others hoses?
Need...