    Sony SRX-611 emergency stop

    Hello First of all you have to write you own system program. It is almost the same which gave sony but you have to add your procedure: I1ON I =1 END Then task program should look like this: INT:I WHILE I=0 CODE ENDW I hope it will help you
  2. PiotrOrlik

    Sony SRX-611 emergency stop

    Hello I am also owner of robots from closed Nokia factory. I think that you might have mechanical problem. Once I was looking information about servos in documentation and accidentally I noticed information that if someone take out motor from the arm(“second” arm) there is no possibility to...
  3. PiotrOrlik

    Sony SRX-611 emergency stop

    Hello, You should contact with Mr Wolf from Germany. He works for company Janomeie witch overtake Sony Robotics His e-mail: wolf@janomeie-europe.de
  4. PiotrOrlik

    Sony SRX-611 emergency stop

    OK, I solved the problem. I wired the pins 1-2 and 3-4 separately. If you wire all the four together it will cause the F1 fuse blow.
  5. PiotrOrlik

    Sony SRX-611 emergency stop

    Hello niko08. What did you mean by "A wrong wiring in the safety connector was blown the fuse"? I have the same problem that you had (I connected pins 1-4 and 9-13 together and I received E342). I also got the fuse blown as well. Could you tell me what you had done to make it work? Did you...