Hi Guys
The Temp Sensor is PT100, it measures 110 ohm which means it is OK, also flow meter has mechanical counter on it and showing flow around 40K meters, since it installed in 2012 and kept measuring since that time.
AMTRON has battery inside it and also gets power from M-BUS, all 180...
Hi,
I have a project where Aquametro BTU calculator AMTRON x-50 is used, about 180 PCS, and AMBUS net 250.
The system installed in 2012 but not commissioned tell this moment, i am trying to start it up, the first issue I faced that AMTRON x-50 doesn't read temp sensors or flow pulses, if you...