Found the problem, an incorrectly ranged flowmeter based on logic changes during the annual (set to 15,000 gpm rather than 25,000). We ended up using an ultrasonic meter on the pipe, ran the unit and saw the discrepancy. Reranged the meter to the correct setting and the unit performs as expected.