  1. lukitorio

    Anyone can help how to solve my problem quickly??

    Thanks for the answers of my problem. However the equalizing line was there originally but lots of problems were happened befor I was joined with the company. The main problem was liquid entrance to the compressors and loss of oil due to migration from "run" to "off" line. At...
  2. lukitorio

    Anyone can help how to solve my problem quickly??

    We had chiller unit to chill the water to provide 4 degC for Oil Fractionation system. The chiller consist of two circuits, where one circuit has three compressors and the other has two compressors. The compressors are come from Carlyle Compr. 06EA599600 (it was 06EA299600 before). Yes the...
  3. lukitorio

    Need advice to solve our Refrigeration System

    We had chiller unit to chill the water to provide 4 degC for Oil Fractionation system. The chiller consist of two circuits, where one circuit has three compressors and the other has two compressors. The compressors are come from Carlyle Compr. 06EA599600 (it was 06EA299600 before). Yes the...