saplanti,EmmanuelTop,georgeverghese,MJCronin,don1980 Thank you all for the detailed clarifications and recommendations.
I knew from the beginning that this discharge piping arrangement is not the recommended way and to reaffirm my thoughts i presented it before you guys and BTW the sketch i...
Dear all,
Please see attachment for my query related with discharge pipe routing of PSV on a 70BarG Boiler Drum.
There are two PSV's on the drum and outlet piping has to be connected to a Silensor to meet the environmental sound limits.
As there is a limitation (approved by law for this...