    100% Outside Air

    Lets keep it simple, your application is not rocket science 1st, your CFM required is dictated by your total sensible load and the temp you want to maintain in the room at the supplly air temp you plan to provide. it is simply found as Rm CFM = Room BTHU QS / 1.08 ( Trm - Tsa ) 2nd, beause...