Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Recent content by davemccombs

  1. davemccombs

    Chill water piping and B31.2

    Thanks bvi. Problem resolved. I was able to justify that this piping installation is catagory D and thus reducing the hydrotesting pressure required to 1.5 times operating pressure.
  2. davemccombs

    Chill water piping and B31.2

    Hello jt. No, I'm not worried about the welds. I have qualified a welder on the procedure and we're performing 10% x-ray, so we're turning out a great product for the client. I guess my real issue is with the hydro-test requirments. The weakest point in the system is <100psi. I will be...
  3. davemccombs

    Chill water piping and B31.2

    I am currently fabricating 4" sch 40 carbon steel pipe for an HVAC unit to be located off-shore. My client is holding me to B31.3 and APR RP-14E on fitup,welding, installation and testing since this will be installed off-shore in a refinery/production environment. This piping will have no more...