  1. buckeye2740

    MCA

    MCA does not necessarily include the full 25% markup on continuous load. The manufacturer takes the evaporator fan, the condensor fan, and the compressor and adds them together. They then add 25% for the largest motor of the group which is almost always the compressor. This number is called...