Recent content by berdindc

  1. berdindc

    Stainless Steel Anchor Bolts

    Thanks you sirs. Intend to use threaded bolts with tack welded nut due to large base moments. That's the plan, until the SS gets v.E.'ed out of the project. I am designing some exterior Structural SS elsewhere on this project..any good references by AISC? I have a Euro Inox publication.
  2. berdindc

    Stainless Steel Anchor Bolts

    Dik, We typically use J-bolts at columns where uplift is not a problem. Columns where the anchor bolts really don't do much other than provide erection stability. Columns with uplift/moments we will use threaded bolts with nuts. Oldrunner, AISC Design Guide #1 and/or ACI 318 Appendix D...
  3. berdindc

    Stainless Steel Anchor Bolts

    Great, thanks for the input. The Portland Bolt website was perfect. I am going to specify the bolts with 90 degree bends. 1" diameter, ASTM A304, minimum yield stress Fy=35 ksi. I believe that should be sufficient to ensure the contractor is getting the right material.
  4. berdindc

    Stainless Steel Anchor Bolts

    Hi, Stainless steel bolts for a WF canopy column. Architectually exposed, architect wants to see the bolts. Right now I'm thinking A316L type 70. I'm having a hard time finding some good values of Fy and Fu and E to use in my calculations. But I am learning a lot about stainless steel...